Yuasa NP batteries utilise the latest advance design Oxygen Recombination Technology. Yuasa have applied their 80 years experience in the lead acid battery field to produce the optimum design of Sealed Valve Regulated Lead Acid batteries. Yuasa NP batteries are the most reliable batteries in the world, which is why industry choose Yuasa over any other battery for security, fire, emergency lighting and uninterruptible power source (UPS) applications.
SPECIFICATIONS
| WARRANTY | 12 Months |
| Name | NP24-12I (12V 24Ah) Yuasa General Purpose VRLA Rechargeable Battery |
| Code | NP24-12I |
| Literature | NP_Series march 09.pdf |
| Nominal voltage | 12 |
| AH | 24 |
| AH RATING | 20-hr rate Capacity to 1.75VPC at 20°C |
DIMENSIONS
| Length | 166 |
| Width | 175 |
| Height | 125 |
| Weight | 9 |
TERMINAL TYPE
| Terminal Type | M5(F) |
| Torque | 2.45 |
OPERATING TEMPERATURE RANGE
| Storage (in fully charged condition) | -20°C to +60°C |
| Charge | -15°C to +50°C |
| Discharge | -20°C to +60°C |
STORAGE
| Capacity loss per month at 20°C (approx) | 3 |
CASE MATERIAL
| Standard Option | ABS (UL.94:HB) |
| Flame retardant option (FR) | ABS (UL94:V0) |
CHARGING
| Float charge voltage at 20°C | 2.275 (±1%) |
| Float charge voltage at 20°C | 2.275 (±1%) |
| Float Charge voltage temperature correction factor
(for variations from the standard 20°C) | -3 |
| Cyclic (or Boost) charge at 20°C | 2.42 (±3%) |
| Cyclic (or Boost) charge at 20°C | 2.42 (±3%) |
| Cyclic Charge voltage temperature correction factor
(for variations from the standard 20°C) | -4 |
| Cyclic (or Boost) charge current limit | 6 |
MAXIMUM DISCHARGE CURRENT
SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE
| Internal resistance (according to EN IEC 60896-21) | 22.19 |
| Short-Circuit current (according to EN IEC 60896-21) | 656 |
IMPEDANCE